Basic Info.
Type
Self-Starting Diesel Generator
Installation Method
Fixed
Cooling Method
Water Cooling
Output Type
AC Three Phase
Conditions of Use
Land Use
Landuse Type of Unit
Low Noise
Excitation Mode
AC Rotating Exciter
Engine Model
Googol Ptaa1780g7 Engine
Alternator Model
Meccalte Eco43-1ln/4
Controller Model
Deep Sea, Comp, Datakom , etc
Voltages
Low Voltage 380V , 400V ,Adjustable
Certificates
CE,ISO.BV,GOST,TUV,SGS,etc
Warranty
1 Year or 1000 Working Hours
Prime Power
800kw 1000kVA
Canopy Types
Silent ,Container,Trailer ,etc
Option
ATS,Circuit Breaker,Parallel, Remote Controlpanels
Lowest Fuel Consumption Ratio
198.40g/Kw.Hr
Transport Package
Poly Plastic Firm/ Wooden Package
Specification
ISO8528, CE, GOST, etc
Product Description
Container 800kW 1000kVA Black Start Emergency Diesel Generator setPerformance Feature
Engine and alternator shall be mounted on a same frame steel skid.
Built-in damper for anti-vibration.
World most famous brand diesel engine.
World famous brand AC alternator.
Advanced and reliable control module<o: P>
Full range protection function and alarm shutdown feature.
Alternator Feature
Brush-less, 4 poles, rotation magnet.
IP21-23(NEMA1) enclosure is standard for all industrial alternators.
The insulation system is Class H
Simple installation and maintenance, with easy access to terminals, rotating diodes and coupling bolts.
Wide range of flange adaptors and single bearing disc coupling.
Standard 2/3 pitch windings avoid excessive neutral currents
AVR auto voltage regulator, auto exciter, auto adjustment
Standard Accessory
Common steel base frame, Damper, Exhaust silencer, Flexible pipe, Battery and connecting wires, Operation manual and document.
Optional Accessory
Engine coolant and oil heater, Alternator space heater, Cooling for heat exchanger, Control system with RS232/485 communication interface, Battery charger by main supply, Fuel-water separator, Daily fuel tank, ATS & paralleling system, and Moving Trailer.
Silent Canopy Description
Standard Accessory:
Steel Weatherproof Canopy
Built In Fuel Tank For 8 Hours Running
Built In Control Panel
Built In Start Battery
Power Output Rapid Insert
Windows for Looking
Air Louver for Intake & Exhaust
Exhaust Gas Silencer
Soundproof Type
Quality Warranty Period:
All equipment is guaranteed for a period of 1000 hours running or 12 months from the date when the generator set has been delivered from the factory.
ATS SYSTEM
For emergency power usage in building, Auto transfer switch (ATS) is essential. ATS can automatic transfer load from Mains power supplying to Emergency power. In normal, when the Main power supplying failure or voltage drop below 80% of normal voltage, ATS will auto start Emergency generator set after a preset time of 0-10 sec (adjustable according to the users). Once generator reach at rated speed, the ATS will transfer the load to emergency generator sets automatically
Generator Model | HGM1100 |
Genset Prime Power | 800kW/1000kVA |
|
Engine Ratings: |
Engine Speed | (RPM) | 1500 |
Generator set Frequency | (Hz) | 50 |
Engine Standby Power (LTP) | (kW) | 931 |
Engine Prime Power (PRP) | (kW) | 847 |
Engine Continuous Power (COP) | (kW) | 677 |
Single Fan Power | (kW) | 7.5 |
Single Fan Consumption | (kW) | 7 |
Quantity of Fan | (Sets) | 4 |
All Fan Consumption | (kW) | 28 |
Engine Net Standby Output (LTP) | (kW) | 931 |
Engine Net Prime Output (PRP) | (kW) | 847 |
Engine Net Continuous Output (COP) | (kW) | 677 |
BMEP for Standby Output | (bar) | 25.48 |
BMEP for Prime Output | (bar) | 23.16 |
BMEP for Continuous Output | (bar) | 18.52 |
Typical Generation Standby Output | (kVA) | 1100 |
Typical Generation Standby Output | (kW) | 880 |
Typical Generation Prime Output | (kVA) | 1000 |
Typical Generation Prime Output | (kW) | 800 |
Typical Generation Continuous Output | (kVA) | 800 |
Typical Generation Continuous Output | (kW) | 640 |
Typical Alternator Efficiency | ≥ | 94.5% |
Power Factor | | 0.8 |
Speed droop (static) elect. Gov. | | 0-5% |
Governing standards to ISO 8528 Parts 1 and 5 | | G3 |
Max. step load acceptance, 1st step(% Prime Output) | | 55% |
|
Basic Performance Datasheet |
Aspiration Type | | Turbocharger, air-air after-cooler |
Injection Type | | Direct Injection |
Configuration | | Vee |
No. of Cylinders | | 16 |
Displacement | (liters) | 19.2 |
Bore | (mm) | 128 |
Stroke | (mm) | 142 |
Compression Ratio | | 14.6:1 |
Piston Speed | (m/s) | 7.10 |
Rotation Direction (from flywheel) | | Counter Clockwise |
Number of Flywheel Teeth | | 204 |
Flywheel House Size | | SAE0-18 |
|
Lubrication System |
Lube Oil Specification | | AFI-CF4 |
Oil Capacity | ( Liters) | 72 |
Max. Permissible Oil Temperature | (°C) | 110 |
Low Oil Pressure Warning | (kPa) | 200 |
Low Oil Pressure Shutdown | (kPa) | 160 |
Oil consumption (as % of fuel consumption) | | ≤0.5 |
|
Cooling System |
Coolant Capacity for Engine | ( Liters) | 26 |
Max. Permissible Temperature | (°C) | 90 |
Max. Coolant Warning Temperature | (°C) | 95 |
Max. Coolant Shutdown Temperature | (°C) | 105 |
Thermostat Open Temperature | (°C) | 71 |
Radiator Cooling Flow | (m³/min) | 1320 |
Flow of Coolant pump | (m³/h) | 51.96 |
Heat dissipation (engine radiator) | (kW) | 446 |
Heat dissipation (convection) | (kW) | 68 |
Radiator Model | | PSCN7002 |
|
Fuel System |
Governor Type | | Electrical Control |
Engine Output at generator set prime output | (kW) | 847 |
Fuel Consumption at 25% of generator set prime output | (l/h) | 56.76 |
Fuel Consumption at 50% of generator set prime output | (l/h) | 102.32 |
Fuel Consumption at 75% of generator set prime output | (l/h) | 150.74 |
Fuel Consumption at 100% of generator set prime output | (l/h) | 201.67 |
Lowest Fuel Consumption Ratio | g/kW.hr | 198.40 |
|
Intake & Exhaust System(On Standby Output) |
Combustion Air Consumption | (m³/min) | 69.84 |
Max. Intake Restriction | (Kpa) | 5 |
Max. Exhaust Temperature(Before Turbo) | (°C) | 696 |
Max. Exhaust Temperature(After Turbo) | (°C) | 505 |
Max. Exhaust Back Pressure | (Kpa) | 5 |
Exhaust Gas Flow | (m³/min) | 85.36 |
Exhaust Flange Diameter | (mm) | 2*150 |
|
Electrical System |
Charging Alternator Voltage | (V) | 28 |
Charging Alternator Capacity | (A) | 55 |
Starting Voltage | (V) | 24 |
Starting Motor Capacity | (kW) | 1*9 |
Minimum Battery Capacity | (Ah) | 2*200 |
Minimum Temperature for Unaided Cold Start | (C) | 10 |
|
Engine Dimension |
Length | (mm) | 1950 |
Width | (mm) | 1389 |
Height | (mm) | 1162 |
Engine Dry Weight w/o Cooling System | (kg) | 2250 |
Note: |
1,All engine parameters are in accordance with ISO3046, ISO8528 2,All engine parameters are based on 25°C / 100kPa environment condition 3,No power decrease with below 40ºC environment temperature and 1500 meter altitude 4,More than 40ºCand 1500m above sea level , decrease 2% per 10ºC , and 4% per 300m 5,At calorific value 42700 kJ/kg + 5%, density 0,835 kg/dm3 , temperature 280 K 6,Above data is only the testing data in our laboratory, it can't used to be the data on all contract Alternator | Alternator model | MGA400-800-4SF | Rating Voltage(V) | 400/230V,380/220V adjustable | Rating Capacity(KW/KVA) | 800/1000 | Eff.% | 95.1% | Power Factor | 0.8 | Exciting type | Brushless self-exciter AVR | Voltage regulation | ±1% | No. of Phase | 3 phase 4 wire | Enclosure Class | IP21 | Class of Insulation | H |
| Standard Accessory | Battery | 4X150AH 12V | Battery Wires | 1 set | Flexible Pipe | 2*6 inch | Industry Silencer | 2*6 inch | Optional Accessory | VCB Breaker Panel | 1600A | Fuel Tank | 1000 Liter | Fuel-water Separator | | Heater | Coolant & Oil Heater |
|
For more products, please visit our showroom honnydg.en.made-in-china.com
For more details, please visit our website honnydg.en.made-in-china.com
Address:
No. 2 Industry North Road, North Industrial Park, Songshan Lake, Dongguan, Guangdong, China
Business Type:
Manufacturer/Factory, Other
Business Range:
Agriculture & Food, Auto, Motorcycle Parts & Accessories, Construction & Decoration, Electrical & Electronics, Industrial Equipment & Components, Instruments & Meters, Light Industry & Daily Use, Metallurgy, Mineral & Energy, Service, Transportation
Management System Certification:
ISO 9001, ISO 9000, ISO 14001, ISO 14000, SA 8000
Company Introduction:
Guangdong Honny Power-Tech Co., Ltd was founded in 1992 and has been one of the leading OEM manufacturer and supplier of power generator and Power Plant within the range of 16kW to 50MW. Honny Power incorporation of Googol Engine-Tech., Ltd. Is committed to provide efficient cost effective clean energy power solution.
We Honny Power specialized in assembly, design, sales, installation and maintenance of diesel generators, natural gas generators, biogas generators, biomass generators, dual fuel generators, diesel power plant and gas power plant. Diesel engines and Gas engines with high and middle speed. Sound and weather proof canopy, Special container, Trailer type power generator, Transformer substation, synchronization and ATS Panels are in related products to provide one window solution for our customers. We have vast experience to design install and maintain power plants around the world with our best world class expertise and engineers. We establish international manufacturing standard, structure and highly qualified staff to maintain quality.
In order to meet rapidly growing demand of our power generators from local and international markets around the world, Honny set up 2 wholly-owned large-scale manufacturing factories, 2 R&D design centers. And there are sales and after-sales service centers in major cities in China.
Under 25 years of tireless work and painstaking efforts, Honny reelected for five consecutive years in China′s best power solutions integrator, and won the Guangdong high-tech enterprises, Guangdong Famous Brand, Guangdong Top Brand, Dongguan Top 50 private enterprises, Dongguan enterprise of observing contract and valuing credit, Dongguan patent nurturing enterprise, Dongguan private technology enterprises, the founder Wen Guosheng won the Dongguan inaugural honor outstanding private entrepreneurs.